Feature
1) 4/8/16 Style B (Class B) Initiating Device Circuits (IDCs).
- All zones accept two-wire smoke detectors and any normally-open contact devices.
- Zones 1 4/8/16 configured as general alarm zones.
2) All circuits are power-limited and supervised, meeting the latest ULC requirements using fuseless technology.
3) Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
4) NACs may be programmed:
- Silenceable
- Non-Silenceable
- Auto-Silence (program 5 to 20 minutes)
5) 1.25 amps of NAC power
6) 3.0 amps of total system power
7) Alarm, Trouble and Supervisory, Form-C relays standard.
8) 24-volt operation
9) Resettable four-wire smoke detector power @ 500 mA
10) Non-resettable power @ 500 mA
11) Integral battery charger capable of charging up to 18 AH batteries (batteries over 4 AH require use of the external battery backbox, or ULC listed equivalent).
12) One-man walk-test programmable for silent or audible test
13) Disable/Enable control per IDC
14) Reverse polarity protection
15) Control buttons:
- Mode
- Test
- ACK (Acknowledge) Alarm Silence
- Reset
16) Meet UL864, EN-54 standard.
17) LED indicators:
- AC Power (green & yellow LED)
- Fire Alarm (red LED)
- Trouble (yellow LED)
- Supervisory (yellow LED)
- Signal Silence (yellow LED)
- Battery Power (green & yellow LED)
- Zone Disable (yellow LED)
- NAC Fault (yellow LED)
- NAC Disable (yellow LED)
- 4/8/16 Zone Alarm (one for each zone) (red LED)
- 4/8/16 Zone Trouble (one for each zone) (yellow LED)
- Earth Fault (on circuit board)
- Battery Fault (on circuit board)
- Charger Fault (on circuit board)
Specifications
AC Power: AC220V±10% 50Hz, 2.0 amps, minimum 14 AWG wire (2.0 mm²) with 600-volt insulation.
Battery: Sealed lead-acid batteries only, Maximum charging circuit: 27.6VDC @ 0.8 amp for normal flat charge, Maximum battery charger capacity: 18AH battery
NOTE: two 4AH batteries can be housed in the cabinet. Larger batteries require a separate battery box.
Total 24 V system power: 3.0 amps
Notification appliance (signal) power: 2.5 amps
Maximum current per NAC: 1.25 amps (expandable to 2.5 amps)
Auxiliary Outputs: - Resettable four-wire smoke detector power @ 500 mA
- Non-resettable power @ 500 mA
- Integral Form-C Alarm, Trouble and Supervisory relays, rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)
NOTE: Total current for auxiliary power outputs and two NACs must not exceed 3.0 amps.
Dimensions: 320×260×80mm (length × width × depth)
Using Environment: Temperature: 10°C~+50°C.
Related Humidity: ≤95% (40±2°C)
Orena Sales and Service
Shenzhen Orena Photonic Technology Co., Ltd
Orena Bldg, Zhong'an Industrial Park, Longjing Road, Nanshan District, Shenzhen, 518055, China
Tel: 86.755.2678.7499
Fax: 86.755.2678.7499
Conventional Fire Alarm Control Panel,alarm control panel,fire alarm panel
Other Products from this Supplier
See more
Fire Alarm Control Panel, Alarm Control Panel, Fire Alarm Panel products from this supplier.
Products
- irrigation control [6]
- smoke alarm [6]
- smoke detector [6]
- heat detector [6]
- fire alarm control panel [9]
- manual call point [3]
- modules [5]
- sounder & strobe [3]
- remote announciator [3]
- Handheld Player [1]
- Others [1]
Company Info
Shenzhen Orena Photonic Technology Co., Ltd.
[China (Mainland)]
[Verified Member]
City: Shenzhen
Province/State: Guangdong
Country/Region : China (Mainland)
Business Type:Manufacturer
Online Postings: Products